(2) The appropriate ratio should be selected according to the magnitude of the current to be measured, otherwise the error will increase.
(3) The secondary winding is absolutely not allowed to open the circuit, otherwise the core will heat up and burn the coil due to excessive saturation magnetization of the core. At the same time, the magnetic circuit is excessively magnetized, which increases the error. When the secondary winding is open, it will also generate a high induced electromotive force (up to several hundred volts), which is likely to cause an electric shock. Therefore, the secondary winding end of the current transformer is equipped with a short-circuit switch to prevent an open circuit.
(4) The secondary winding end must be grounded.
(5) The load impedance of the secondary winding end should not exceed the specified value to reduce the error. Usually the rated capacity is given on the nameplate of the current transformer, then the formula can be The allowable impedance value of the secondary side is obtained.
October 25, 2024
October 25, 2024
September 27, 2023
September 25, 2023
September 26, 2023
September 26, 2023
Envoyer à ce fournisseur
October 25, 2024
October 25, 2024
September 27, 2023
September 25, 2023
September 26, 2023
September 26, 2023
Privacy statement: Your privacy is very important to Us. Our company promises not to disclose your personal information to any external company with out your explicit permission.
Fill in more information so that we can get in touch with you faster
Privacy statement: Your privacy is very important to Us. Our company promises not to disclose your personal information to any external company with out your explicit permission.